1) Figure below shown the schematic diagram of 3-phase radial transmission system. The ratings and reactances of the various components are shown, along with the nominal transformer line voltages. A load of 50 MW at 0.8 p.f. lagging is taken from the 33-kV substation which is to be maintained at 30 kV. It is required to calculate the terminal voltage of the synchronous machine. The line and transformers may be represented by series reactances. The system is three-phase. 11 kV 132 kV 50MVA X = 10% Line j100 132 kV 33 kV 50 MVA X=12% 30kV 50MW 0-8p.f. lagging

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.48P: With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a...
icon
Related questions
Question
1) Figure below shown the schematic diagram of 3-phase radial transmission
system. The ratings and reactances of the various components are shown, along with
the nominal transformer line voltages. A load of 50 MW at 0.8 p.f. lagging is taken
from the 33-kV substation which is to be maintained at 30 kV. It is required to
calculate the terminal voltage of the synchronous machine. The line and transformers
may be represented by series reactances. The system is three-phase.
11 kV 132 kV
50MVA
X = 10%
Line
j100
132 kV 33 kV
50 MVA
X=12%
30kV
50MW
0-8p.f.
lagging
Transcribed Image Text:1) Figure below shown the schematic diagram of 3-phase radial transmission system. The ratings and reactances of the various components are shown, along with the nominal transformer line voltages. A load of 50 MW at 0.8 p.f. lagging is taken from the 33-kV substation which is to be maintained at 30 kV. It is required to calculate the terminal voltage of the synchronous machine. The line and transformers may be represented by series reactances. The system is three-phase. 11 kV 132 kV 50MVA X = 10% Line j100 132 kV 33 kV 50 MVA X=12% 30kV 50MW 0-8p.f. lagging
Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning