5. Given a balanced 3-ph 34.64 kV system serving a 120 MVA unity pfload, which can be modelled as balanced 3-wire Zy = (346420° +34642-120° +34642120°) (120) 2 wve-connected impedances. (a) Find Z,. сока -15 (b) If = 34.64 kV and S-10 MVA find V, and Z, in pu. LBase Va= 34.64 7X Zu 600 = 538 = 10

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.14MCQ: The instantaneous power absorbed by the load in a single-phase ac circuit, for a general R LC load...
icon
Related questions
icon
Concept explainers
Question
5. Given a balanced 3-ph 34.64 kV system serving a 120 MVA unity pf load, which can be modelled as balanced 3-wire
wve-connected impedances. X
Zy = (346420° +34642-120° +34642120°)
(a) Find Ży.
LOKR
(120)
(b) If = 34.64 kV and S
LBase
Va=
34.64x
-150
-10 MVA find V, and Z, in pu.
Zu 600
Vú
Zy = V₁²
538
= 102
Transcribed Image Text:5. Given a balanced 3-ph 34.64 kV system serving a 120 MVA unity pf load, which can be modelled as balanced 3-wire wve-connected impedances. X Zy = (346420° +34642-120° +34642120°) (a) Find Ży. LOKR (120) (b) If = 34.64 kV and S LBase Va= 34.64x -150 -10 MVA find V, and Z, in pu. Zu 600 Vú Zy = V₁² 538 = 102
Expert Solution
steps

Step by step

Solved in 3 steps with 1 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning