A power station has a load cycle as under: 260 Mw for 6 hours; 200 mw for 8 hours; 160 Mw for 4 hours; 100 Mw for 6 hours. If the power station is equipped with 5 sets of 75 Mw each, the capacity factor of the power station is: 0.451 O 0.611 0.489 0.621

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.31P: Consider two interconnected voltage sources connected by a line of impedance Z=jX, as shown in...
icon
Related questions
Question
A power station has a load cycle as under: 260 Mw for 6 hours; 200 mw for 8 hours;
160 Mw for 4 hours; 100 Mw for 6 hours. If the power station is equipped with 5
sets of 75 Mw each, the capacity factor of the power station is:
0.451
0.611
0.489
0.621
Transcribed Image Text:A power station has a load cycle as under: 260 Mw for 6 hours; 200 mw for 8 hours; 160 Mw for 4 hours; 100 Mw for 6 hours. If the power station is equipped with 5 sets of 75 Mw each, the capacity factor of the power station is: 0.451 0.611 0.489 0.621
The Daily load factor of the station is:
71.6%
70.5 %
71%
70.8%
Transcribed Image Text:The Daily load factor of the station is: 71.6% 70.5 % 71% 70.8%
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
HVDC
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning