Q2- 100 KVA, (6600/330) ,single-phase transformer, the primary connected to supply voltage 100 V and the secondary side short-circuit. The transformer drawn 10 A and 436 watt. calculate the voltage applied to primary winding at full load with 0.8 lag p.f to make secondary voltage 330 V. ANS. 6734 V

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.9P
icon
Related questions
Question
Q2-100 KVA, (6600/330) ,single-phase transformer, the primary connected to supply
voltage 100 V and the secondary side short-circuit. The transformer drawn 10 A and 436
watt. calculate the voltage applied to primary winding at full load with 0.8 lag p.f to make
secondary voltage 330 V.
ANS. 6734 V
Transcribed Image Text:Q2-100 KVA, (6600/330) ,single-phase transformer, the primary connected to supply voltage 100 V and the secondary side short-circuit. The transformer drawn 10 A and 436 watt. calculate the voltage applied to primary winding at full load with 0.8 lag p.f to make secondary voltage 330 V. ANS. 6734 V
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L