Required information A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.310 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 450 W from the surroundings. The heat exchanger loses no heat to the environment. 26°C 42°C Water 18°C 1.2 MPa 65°C 2 (3) Condenser ↑gin Expansion valve Evaporator Compressor 60 kPa -34°C 4 1 Οι Determine the quality of the refrigerant at the evaporator inlet. (Take the required values from saturated refrigerant-134a tables.) (Round the final answer to four decimal places.) The quality of the refrigerant at the evaporator inlet is

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter22: Condensers
Section: Chapter Questions
Problem 7RQ: When a standard-efficiency air-cooled condenser is used, the condensing refrigerant will normally be...
Question
Required information
A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by
rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.310 kg/s and leaves at 26°C. The
refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and
-34°C and the compressor is estimated to gain a net heat of 450 W from the surroundings. The heat exchanger loses no
heat to the environment.
26°C
42°C
Water
18°C
1.2 MPa
65°C
2
(3) Condenser
↑gin
Expansion
valve
Evaporator
Compressor
60 kPa
-34°C
4
1
Οι
Determine the quality of the refrigerant at the evaporator inlet. (Take the required values from saturated refrigerant-134a tables.)
(Round the final answer to four decimal places.)
The quality of the refrigerant at the evaporator inlet is
Transcribed Image Text:Required information A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.310 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 65°C and leaves at 42°C. The inlet state of the compressor is 60 kPa and -34°C and the compressor is estimated to gain a net heat of 450 W from the surroundings. The heat exchanger loses no heat to the environment. 26°C 42°C Water 18°C 1.2 MPa 65°C 2 (3) Condenser ↑gin Expansion valve Evaporator Compressor 60 kPa -34°C 4 1 Οι Determine the quality of the refrigerant at the evaporator inlet. (Take the required values from saturated refrigerant-134a tables.) (Round the final answer to four decimal places.) The quality of the refrigerant at the evaporator inlet is
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning