Two generators are connected in parallel to the low voltage side of a transformer. Generators Gl and G 2 are each rated at 50 MVA, 13.8 kV, with a subtransient resistance of 0.2 pu. Transformer T1 is rated at 100 MVA, 13.8/115 kV with a series reactance of 0.08 pu and negligible resistance. Assume that initially the voltage on the high side of the transformer is 120 kV, that the transformer is unloaded, and that there are no circulating currents between the generators. Calculate the subtransient fault current that will flow if a 3 phase fault occurs at the high-voltage side of transformer 美。 AY G, ratings: sÓ MVA G2 ratings: 50 MVA T, ratings: 100 MVA 13.8/11 3AV X - 0.08 pu 13.8 AV 13.8 AV X"- 0.20 pu X"- 0.20 pu

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.26P: A bank of three single-phase transformers, each rated 30MVA,38.1/3.81kV, are connected in Y- with a...
icon
Related questions
Question
Two generators are connected in parallel to the low voltage side of a
transformer. Generators G1 and G 2 are each rated at 50 MVA, 13.8 kV,
with a subtransient resistance of 0.2 pu. Transformer T1 is rated at 100
MVA, 13.8/115 kV with a series reactance of 0.08 pu and negligible
resistance. Assume that initially the voltage on the high side of the
transformer is 120 kV, that the transformer is unloaded, and that there are
no circulating currents between the generators. Calculate the subtransient
fault current that will flow if a 3 phase fault occurs at the high-voltage
side of transformer
AY
Gz ratings:
50 MVA
G, ratings:
số MVA
13.8 KV
X" = 0.20 pu
T, ratings:
100 MVA
13.8/113 V
X - 0.08 pu
13.8 KV
X" - 0.20 pu
Choose the per-unit base values for this power system to be 100 MVA
and 13.8 kV
Transcribed Image Text:Two generators are connected in parallel to the low voltage side of a transformer. Generators G1 and G 2 are each rated at 50 MVA, 13.8 kV, with a subtransient resistance of 0.2 pu. Transformer T1 is rated at 100 MVA, 13.8/115 kV with a series reactance of 0.08 pu and negligible resistance. Assume that initially the voltage on the high side of the transformer is 120 kV, that the transformer is unloaded, and that there are no circulating currents between the generators. Calculate the subtransient fault current that will flow if a 3 phase fault occurs at the high-voltage side of transformer AY Gz ratings: 50 MVA G, ratings: số MVA 13.8 KV X" = 0.20 pu T, ratings: 100 MVA 13.8/113 V X - 0.08 pu 13.8 KV X" - 0.20 pu Choose the per-unit base values for this power system to be 100 MVA and 13.8 kV
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 4 steps with 2 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning