Two identical three – phase Y – connected alternator A and B share equally a load of 10MW at 33kV and 80% lagging pf. The synchronous reactance of each machine is 4 ohms per phase and thew armature resistance is negligible. Alternator A has its filed excitation adjusted to carry 125 A lagging current, what is the current supplied by alternator B? a. 96 A b. 97 A b. 98 A d. 95 A

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter31: Three-phase Alternators
Section: Chapter Questions
Problem 1RQ: What conditions must be met before two alternators can be paralleled together?
icon
Related questions
Question

Two identical three – phase Y – connected alternator A and B share equally a load of 10MW at 33kV and 80% lagging pf. The synchronous reactance of each machine is 4 ohms per phase and thew armature resistance is negligible. Alternator A has its filed excitation adjusted to carry 125 A lagging current, what is the current supplied by alternator B?

a. 96 A b. 97 A

b. 98 A d. 95 A

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning