3. A short 3-phase transmission line delivers 1000 KVA at 10kV, 0.8 power JS factor lagging to a balanced load. The resistance per conductor is 40 and the Y reactance is 60. calculate the voltage and current at the sending-end, and AS vs also calculate the voltage regulation.
3. A short 3-phase transmission line delivers 1000 KVA at 10kV, 0.8 power JS factor lagging to a balanced load. The resistance per conductor is 40 and the Y reactance is 60. calculate the voltage and current at the sending-end, and AS vs also calculate the voltage regulation.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.23P: Figure 3.32 shows the oneline diagram of a three-phase power system. By selecting a common base of...
Related questions
Question
I need a solution plz and thank u
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 3 steps with 8 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning