In a three-phase, Y-connected, 750-kVA, 1732-V, synchronous generator afield current of 20 A at the rated speed produces a current of 300 A onshort circuit and a voltage of 1732 V on open circuit. The resistance betweenany two terminals of the generator is 0.8 R. Determine the synchronousreactance of the generator. The rotational loss is 20 kW. Using the per-unitsystem, determine the voltage regulation and the efficiency of the generatorwhen it delivers the rated load at its rated voltage and unity power factor.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.48P
icon
Related questions
Question

In a three-phase, Y-connected, 750-kVA, 1732-V, synchronous generator a
field current of 20 A at the rated speed produces a current of 300 A on
short circuit and a voltage of 1732 V on open circuit. The resistance between
any two terminals of the generator is 0.8 R. Determine the synchronous
reactance of the generator. The rotational loss is 20 kW. Using the per-unit
system, determine the voltage regulation and the efficiency of the generator
when it delivers the rated load at its rated voltage and unity power factor.

Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning