In the diagram, Load A is rated at 10 amperes, 120 volts. Load B is rated at 5 amperes, 120 volts.
- a. When connected to the 3-wire branch circuit as indicated, how much current will flow in the neutral conductor? __________________
- b. If the neutral conductor should open, to what voltage would each load be subjected, assuming both loads were operating at the time the neutral conductor opened? Show all calculations.
a.
Find the amount of current that flows in a neutral conductor when a circuit is connected to a 3-wire branch circuit.
Answer to Problem 4R
The amount of current that flows in the neutral conductor is
Explanation of Solution
Given data:
The values of current and voltage at Load A are
The values of current and voltage at Load B are
The total voltage of the system is
Calculation:
From the given data, the values of current to Load A and Load B are not equal. Therefore, it is an unbalanced load.
For an unbalanced load, the current through the neutral conductor is calculated as follows:
Substitute
Conclusion:
Thus, the amount of current that flows in the neutral conductor is
b.
Find the voltage of each load when the neutral conductor is open.
Answer to Problem 4R
The voltage of Load A is
Explanation of Solution
Formula used:
Write an expression to calculate the resistance.
Here,
Calculation:
Substitute
Substitute
When the neutral conductor is open, Load A and Load B are connected in series. Therefore, the total resistance is calculated as follows:
Substitute
Rearrange equation (2) to find
Substitute
Rearrange equation (4) to find
For the series connected load, the current is same for both Load A and Load B.
Substitute
Substitute
Conclusion:
Thus, the voltage of Load A is
Want to see more full solutions like this?
Chapter 17 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Additional Engineering Textbook Solutions
ELECTRICITY FOR TRADES (LOOSELEAF)
Programmable Logic Controllers
Introductory Circuit Analysis (13th Edition)
Microelectronics: Circuit Analysis and Design
Fundamentals of Applied Electromagnetics (7th Edition)
Electrical Engineering: Principles & Applications (7th Edition)
- 22. Generally, ungrounded (hot) conductors can be any color except ____. Select one: A. WHITE, GRAY, OR RED B. RED, YELLOW, OR GRAY C. YELLOW, RED, OR GREEN WITH YELLOW STRIPES D. WHITE, GRAY, GREEN, OR, GREEN WITH YELLOW STRIPE(S)arrow_forwardLow-voltage conductors. a. are not powerful enough to cause death from electrocution b. must exceed 480V to cause death C. are responsible for most electrocution deaths due to the frequency of contact d. are unlikely to cause injury if rubber-soled shoes are wornarrow_forwardAn aluminum conductor with a diameter of 0.2 in. was badly damaged during a short-circuit. It was decided that a hard-drawn copper conductor with the same resistance will be used in its place. What should be the diameter of this copper conductor?arrow_forward
- 12. A short circuit describes the condition where there's contact between theA. hot wire and the neutral wire.B. grounded conductor and the grounding wire.C. hot wire and the grounding wire.D. neutral wire and the grounded conductor. I'm not sure if it's the letter A or C, could you help me with the correct answer.arrow_forwardWhat size conductor should be used in a 2-wire system to service a load of 6,500 watts, 150 feet from the generator? The voltage at the load is 120 volts, and the voltage drop should not exceed 2.5 volts. Round to a whole number.arrow_forwarda.2. Which of the following statements about grounding electrode conductors is true?A. They restrict the ground connection.B. They eliminate potential differences between conductive objects and the Earth electrode.C. They facilitate operation of overcurrent protective devices.D. They perform bonding between the Earth and grounded conductors.a.3. Main bonding jumpers are required to be made of _______ or other corrosion-resistant material.A. brassB. aluminumC. copperD. copper-clad aluminumarrow_forward
- When installing grounding electrode conductor at services, it's common to use a single large common grounding electrode conductor and connect multiple grounding electrode conductor to it A. clamps B.jumper C. taps D.screwsarrow_forwardNeed all detailed information and answers. What are three main reasons to install grounds and bonds on an isolated circuit before work is started? When using protective grounds, does the application of the grounding principle control current or voltage? Does all the current in a grounded conductor take the easiest path to earth? What is the bonding principle? When removing protective grounds on an isolated circuit, which set of grounds is more likely to create an arc, the first set or the second set?arrow_forward4. In conceal knob and tubing wiring, the clearance to be maintain between conductors is a. 45 mm b. 76 mm c. 55 mm d. d. 50 mmarrow_forward
- What is the mean of wiringarrow_forwardPls help me answer this . DC Voltage has ______ polarityarrow_forwardb. 63 rule where two different temperatures are encountered for the same conductors 38. An exception to the permits the application of the higher ampacity (lower temperature) if the length of the conductors that enter a higher temperature is not more than 10 ft (3.0 m) or not more than 10% of the total circuit length. C. ampacity rating d. flux rating a. circuit derating b. ampacity derating lood isarrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT